Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 4, 2017, 07:13 AM
  • 16 0753_16 0013_04102017_001416.mp4

Date
10/04/2017
W/O
658233
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00639
PipeID
P13050
Time
12:13 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4990
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN GABRIEL
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
WO_658233_TV16005_SEP2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
16 0753
Downstream MH
16 0013
Dir. of Survey
Downstream
Length Surveyed
10 ft.
Total Length
10 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 16 0753 to 16 0013
MH: 16 0753MH: 16 0013downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 07538 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES10 ft. AMH - Downstream Manhole, Survey Ends - 16 0013

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
8SAV
0MWL
0MWM
8DAGS
10AMH16 0013
0AMH16 0753

Properties (5)

additional_info
SC345982
custom_field_two
3
customer
LACSD
datetime
2017-10-04T00:13:08-07:00
is_lateral_inspection
false