Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2017, 08:29 AM
  • F 0068_F 0067 _09142017_021050.mp4

Date
09/14/2017
W/O
651629
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00035
PipeID
P10153
Time
1:29 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4971
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_651629_TV02199_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0068
Downstream MH
F 0067
Dir. of Survey
Downstream
Length Surveyed
243.1 ft.
Total Length
243.1 ft.
Structural Index
4
Structural Quick
5C3D
Structural Rating
180
O&M Index
2
O&M Quick
412H
O&M Rating
98
Overall Index
3
Overall Quick
Overall Rating
278
Pipe schematic from manhole F 0068 to F 0067
MH: F 0068MH: F 0067downstream0 ft. AMH - Upstream Manhole, Survey Begins - F 00680 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area4.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start4.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start109.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish117.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start240.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish241 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish243.1 ft. AMH - Downstream Manhole, Survey Ends - F 0067

Observation photos (3)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    117.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
4.9SRV
109.3SRV
0AMHF 0068
0MWM
241DAGS
0MWL
240.6SAP
117.4SAP
243.1AMHF 0067
4.9DAGS

Properties (5)

additional_info
SC345963
custom_field_two
2
customer
LACSD
datetime
2017-09-14T01:29:00-07:00
is_lateral_inspection
false