Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2017, 09:40 PM
  • F 0234_F 0255 _09132017_030218.mp4

Date
07/26/2017
W/O
651629
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00035
PipeID
P22105
Time
2:40 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4970
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_651629_TV02199_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
F 0234
Downstream MH
F 0255
Dir. of Survey
Downstream
Length Surveyed
4.1 ft.
Total Length
4.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole F 0234 to F 0255
MH: F 0234MH: F 0255downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 02340 ft. MWM - Water Mark, 50 %of cross sectional area4.1 ft. AMH - Downstream Manhole, Survey Ends - F 02554.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (5)

DistanceCodeObservation
0MWL
4.1AMHF 0255
4.1SAV
0AMHF 0234
0MWM

Properties (5)

additional_info
SC345962
custom_field_two
4
customer
LACSD
datetime
2017-07-26T14:40:11-07:00
is_lateral_inspection
false