Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2015, 11:54 AM
  • H 0367_H 0366_20151117_040958.mp4

Date
11/17/2015
W/O
531052
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00172
PipeID
P10707
Time
3:54 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2864
Sewer Name
H JOINT OUTFALL H - UNIT 2G
City
LOS ANGELES, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_531052_TV02281_OCT2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
H 0367
Downstream MH
H 0366
Dir. of Survey
Downstream
Length Surveyed
450.7 ft.
Total Length
450.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4131
O&M Rating
51
Overall Index
2
Overall Quick
Overall Rating
51
Pipe schematic from manhole H 0367 to H 0366
MH: H 0367MH: H 0366downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 0367 (0354)2.8 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start22.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish22.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start93.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Change333.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"338.6 ft. DAE - Deposits Attached Encrustation, 20 %of cross sectional area, from 09 to 04 o'clock, , within 8 inches of joint: YES340.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"446.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish450.7 ft. AMH - Downstream Manhole, Survey Ends - H 0366 (0409)

Observation photos (1)

  • Deposits Attached Encrustation, 20 %of cross sectional area, from 09 to 04 o'clock,  , within 8 inches of joint: YES

    338.6 ft. - Deposits Attached Encrustation, 20 %of cross sectional area, from 09 to 04 o'clock, , within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
22.5DAE
0MWM
446.3DAGS
338.6DAE
0MWL
0AMHH 0367 (0354)
2.8DAE
340.6TF
93.5TBA
333.2TBA
450.7AMHH 0366 (0409)
22.5DAGS
118.1DAGS

Properties (5)

additional_info
SC205629
custom_field_two
4
customer
LACSD
datetime
2015-11-17T03:54:00-08:00
is_lateral_inspection
false