Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2016, 10:49 AM
  • 19 0099_19 0098_20160311_040619.mp4

Date
03/11/2016
W/O
557968
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00722
PipeID
P15291
Time
2:49 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3222
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
LAKEWOOD, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Routine Assessment
Project
WO_557968_TV19021_2016MAR
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
19 0099
Downstream MH
19 0098
Dir. of Survey
Downstream
Length Surveyed
338.7 ft.
Total Length
338.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
132
Pipe schematic from manhole 19 0099 to 19 0098
MH: 19 0099MH: 19 0098downstream0 ft. AMH - Upstream Manhole, Survey Begins - 19 00990 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start18.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"69.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"120.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"171.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"223 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"272.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4", 4"318.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"335.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish338.7 ft. AMH - Downstream Manhole, Survey Ends - 19 0098

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Finish

    335.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observations (13)

DistanceCodeObservation
223TFC
7DAGS
272.5TFC
335.7DAGS
69.9TFC
0AMH19 0099
318.3TFC
18.9TFC
120.3TFC
0MWM
0MWL
171.6TFC
338.7AMH19 0098

Properties (6)

additional_info
SC305312
custom_field_two
4
customer
LACSD
datetime
2016-03-11T02:49:06-08:00
documentation
PRO-PIPE
is_lateral_inspection
false