Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2016, 08:59 AM
  • 19 0142_19 0141_20160314_030918.mp4

Date
03/14/2016
W/O
557968
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00722
PipeID
P15332
Time
1:59 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3223
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
03
Purpose
Routine Assessment
Project
WO_557968_TV19021_2016MAR
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
19 0142
Downstream MH
19 0141
Dir. of Survey
Downstream
Length Surveyed
142 ft.
Total Length
142 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 19 0142 to 19 0141
MH: 19 0142MH: 19 0141downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 19 01421 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: NO11.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start40 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"42 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"139.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish142 ft. AMH - Downstream Manhole, Survey Ends - 19 0141

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock,  , within 8 inches of joint: NO

    1 ft. - Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: NO

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    11.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
142AMH19 0141
42TFC
0MWL
11.6DAGS
40TF
139.3DAGS
1DAGS
0MWM
0MGOLATERAL AT MH 3 OCLOCK
0MGOLATERAL AT MH 9 OCLOCK
0AMH19 0142

Properties (6)

additional_info
SC305313
custom_field_two
4
customer
LACSD
datetime
2016-03-14T01:59:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false