Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 13, 2018, 12:23 PM
  • 18 0308_18 0307A_12132018_043515.mp4

Date
12/13/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00683
PipeID
P25009
Time
4:23 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1077
Sewer Name
18 LA MIRADA TRUNK, SECTS 1&2
City
LA MIRADA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
20181213MDM_LA_MIRADA_TRUNK_SECTS_1_2
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
18 0308
Downstream MH
18 0307A
Dir. of Survey
Downstream
Length Surveyed
240.9 ft.
Total Length
240.9 ft.
Structural Index
4
Structural Quick
5A41
Structural Rating
66
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
66
Pipe schematic from manhole 18 0308 to 18 0307A
MH: 18 0308MH: 18 0307Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MAG COAT 80% START 8:00 TO 4:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR28 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR29.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM37.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped43.2 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM60.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC75.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM75.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC85.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO, Finish - LONG CIRCUM REBAR85.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active99.2 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM107.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR113.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM124.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM132.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR142.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped160.7 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM177.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO190.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open197.4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM240.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR SPORATIC240.6 ft. MGO - General Observation - MAG COAT 70% FINISH240.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC240.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN240.6 ft. SRC - VISABLE SEVERE AGG from 09 to 03o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC240.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE240.9 ft. AMH - Downstream Manhole, Survey Ends - 5:15AM

Observation photos (15)

  • General Observation - MAG COAT 80% START 8:00 TO 4:00

    0 ft. - General Observation - MAG COAT 80% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES,  - CIRCUM REBAR

    2.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    28 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

    29.1 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

    43.2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    60.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM

    75.2 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    75.2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

    99.2 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    107.4 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

    124.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM

    160.7 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

    177.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

    197.4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

Observations (32)

DistanceCodeObservation
240.6SRCLONG CIRCUM REBAR SPORATIC
2SSSBLISTERING PEELING CONCRETE
240.6MGOMAG COAT 70% FINISH
29.1SRCCIRCUM
60.8SAVSEVERE AGG SPORATIC
142.2TFCCapped
28SRCCIRCUM REBAR
113.4SRVCIRCUM
240.6SAMSEVERE AGG SPORATIC
107.4SRVCIRCUM REBAR
240.9AMH5:15AM
177.1SSS
0AMH4:25AM
197.4SRVCIRCUM
160.7SRCLONG CIRCUM
0MWL
85.5SRCLONG CIRCUM REBAR
75.2SRCLONG CIRCUM
85.5TFActive
124.9SRCLONG CIRCUM
37.1TFCCapped
43.2SRCCIRCUM
240.6MGOConn. @ Mh, 3 O' Clock. OPEN
240.6SRCSEVERE AGG SPORATIC
240.6SSSBLISTERING PEELING CONCRETE
0MWM
0MGOMAG COAT 80% START 8:00 TO 4:00
132.8SRCLONG CIRCUM REBAR
75.2SAMSEVERE AGG SPORATIC
99.2SRVCIRCUM
2.1SRCCIRCUM REBAR
190.7TFOpen

Properties (4)

custom_field_three
LONG & CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2018-12-13T04:23:57-08:00