Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 13, 2018, 09:40 AM
  • 18 0314_18 01267_12132018_015406.mp4

Date
12/13/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00683
PipeID
P26465
Time
1:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1077
Sewer Name
18 LA MIRADA TRUNK, SECTS 1&2
City
LA MIRADA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
20181213MDM_LA_MIRADA_TRUNK_SECTS_1_2
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
18 0314
Downstream MH
18 01267
Dir. of Survey
Downstream
Length Surveyed
244.8 ft.
Total Length
244.8 ft.
Structural Index
3
Structural Quick
5333
Structural Rating
34
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
38
Pipe schematic from manhole 18 0314 to 18 01267
MH: 18 0314MH: 18 01267downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 1:40AM0 ft. MGO - General Observation - MAG COAT 90% START 9:00 TO 3:000 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE10.8 ft. SSS - Surface Spalling, from 11 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE10.8 ft. SAV - Surface Aggregate Visible, from 11 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC16.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE IN SHEETS60.8 ft. MGO - General Observation - MAG COAT 50% START64.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETEIN SHEETS67 ft. SAV - Surface Aggregate Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG70.1 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR88.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC88.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE121.3 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR125.1 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR137.5 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR137.5 ft. MGO - General Observation - MAG COAT 20% START143.4 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - PEELING CONCRETE199.3 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - PEELING CONCRETE244.2 ft. MGO - General Observation - MAG COAT 20% FINISH244.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING BLISTERING CONCRETE244.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG244.8 ft. AMH - Downstream Manhole, Survey Ends - 2:20AM

Observation photos (16)

  • General Observation - MAG COAT 90% START 9:00 TO 3:00

    0 ft. - General Observation - MAG COAT 90% START 9:00 TO 3:00

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE

  • Surface Spalling, from 11 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    10.8 ft. - Surface Spalling, from 11 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Aggregate Visible, from 11 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    10.8 ft. - Surface Aggregate Visible, from 11 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE IN SHEETS

    16.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE IN SHEETS

  • General Observation - MAG COAT 50% START

    60.8 ft. - General Observation - MAG COAT 50% START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETEIN SHEETS

    64.7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETEIN SHEETS

  • Surface Aggregate Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    67 ft. - Surface Aggregate Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    70.1 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    88.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    88.3 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    121.3 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    137.5 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • General Observation - MAG COAT 20% START

    137.5 ft. - General Observation - MAG COAT 20% START

  • Deposits Settled Other,  5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - PEELING CONCRETE

    143.4 ft. - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - PEELING CONCRETE

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - PEELING CONCRETE

    199.3 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - PEELING CONCRETE

Observations (25)

DistanceCodeObservation
244.2MGOMAG COAT 20% FINISH
10.8SSSPEELING CONCRETE
10.8SAVSEVERE AGG SPORATIC
16.6SSSPEELING CONCRETE IN SHEETS
244.2SSSPEELING BLISTERING CONCRETE
70.1SRVCIRCUM REBAR
0MWL
64.7SSSPEELING CONCRETEIN SHEETS
143.4DSZPEELING CONCRETE
137.5SRVLONG & CIRCUM REBAR
88.3SAVSEVERE AGG SPORATIC
0MGOConn. @ Mh, 3 O' Clock. Active
244.8AMH2:20AM
88.3SSSPEELING CONCRETE
199.3DSZPEELING CONCRETE
2SSSPEELING BLISTERING CONCRETE
244.2SAVSEVERE AGG
121.3SRVCIRCUM REBAR
0AMH1:40AM
125.1SRVCIRCUM REBAR
60.8MGOMAG COAT 50% START
67SAVSEVERE AGG
0MGOMAG COAT 90% START 9:00 TO 3:00
0MWM
137.5MGOMAG COAT 20% START

Properties (4)

custom_field_three
VISIBLE REBAR- PEELING CONCRETE IN SHEETS
custom_field_two
2
customer
LACSD
datetime
2018-12-13T01:40:00-08:00