Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2018, 12:25 PM
  • 08 0468_08 0467_12122018_043501.mp4

Date
12/12/2018
W/O
0744161
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00524
Time
4:25 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1076
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20181212MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0468
Downstream MH
08 0467
Dir. of Survey
Downstream
Length Surveyed
442.8 ft.
Total Length
442.8 ft.
Structural Index
5
Structural Quick
5A41
Structural Rating
64
O&M Index
5
O&M Quick
5241
O&M Rating
14
Overall Index
5
Overall Quick
Overall Rating
78
Pipe schematic from manhole 08 0468 to 08 0467
MH: 08 0468MH: 08 0467downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM2 ft. MGO - General Observation - MISSING TILES 40%% START2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR8 ft. DSZ - Deposits Settled Other, 70 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - TILES UNDER FLOW13.1 ft. MGO - General Observation - MISSING TILES 100% START14.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR19.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR CIRCUM22.6 ft. MGO - General Observation - MAG COAT 80% START 10:00 TO 2:0026.7 ft. MGO - General Observation - 26% MISSING TILES START93 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR102.3 ft. MGO - General Observation - MISSING TILES 100% START115.7 ft. MGO - General Observation - 3 ROWS TILES122 ft. MGO - General Observation - 2 ROWS TILES133.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR139.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR149.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR156.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR156.8 ft. MWM - Water Mark, 50 %of cross sectional area156.8 ft. MWL - Water Level, 40 %of cross sectional area172.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR172.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR208.1 ft. MGO - General Observation - 10% MISSING TILES217.5 ft. MGO - General Observation - 100% MISSING TILES START217.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR258.1 ft. MGO - General Observation - 50% MISSING TILES258.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR316.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR316.3 ft. MGO - General Observation - 100% MISSING TILES335.9 ft. MGO - General Observation - 60% MISSING TILES353.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR368.7 ft. MWM - Water Mark, 40 %of cross sectional area368.7 ft. MWL - Water Level, 20 %of cross sectional area442.4 ft. SAM - Surface Aggregate Missing, from 9 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG442.4 ft. MGO - General Observation - MAG COAT 80% FINISH442.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN442.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR442.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR442.4 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. OPEN442.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRISON BEYOUND REBAR442.8 ft. AMH - Downstream Manhole, Survey Ends - 5:25AM

Observation photos (19)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • Deposits Settled Other,  70 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: NO - TILES UNDER FLOW

    8 ft. - Deposits Settled Other, 70 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - TILES UNDER FLOW

  • General Observation - MISSING TILES 100% START

    13.1 ft. - General Observation - MISSING TILES 100% START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    14.4 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR CIRCUM

    19.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR CIRCUM

  • General Observation - MAG COAT 80% START 10:00 TO 2:00

    22.6 ft. - General Observation - MAG COAT 80% START 10:00 TO 2:00

  • General Observation - MISSING TILES 100% START

    102.3 ft. - General Observation - MISSING TILES 100% START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    133.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

    139.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

    149.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    156.8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR

    172.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR

  • General Observation - 10% MISSING TILES

    208.1 ft. - General Observation - 10% MISSING TILES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

    217.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

  • General Observation - 50% MISSING TILES

    258.1 ft. - General Observation - 50% MISSING TILES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    316.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

    353.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

  • Water Mark, 40 %of cross sectional area

    368.7 ft. - Water Mark, 40 %of cross sectional area

Observations (43)

DistanceCodeObservation
353.2SRCCORRISON BEYOUND REBAR
442.4SAMSEVERE AGG
368.7MWM
2MGOMISSING TILES 40%% START
0MWM
258.1MGO50% MISSING TILES
13.1MGOMISSING TILES 100% START
217.5MGO100% MISSING TILES START
442.4MGOMAG COAT 80% FINISH
22.6MGOMAG COAT 80% START 10:00 TO 2:00
139.5SRCBROKEN MISSING REBAR
8DSZTILES UNDER FLOW
26.7MGO26% MISSING TILES START
172.6SRCBROKEN MISSING REBAR
217.5SRCBROKEN MISSING REBAR
442.4MGOConn. @ Mh, 3 O' Clock. OPEN
14.4SRCLONG & CIRCUM REBAR
93SRCBROKEN REBAR
442.4SRCLONG & CIRCUM REBAR
2SAMSEVERE AGG
156.8SRCLONG & CIRCUM REBAR
172.7SRCBROKEN MISSING REBAR
2SRCLONG & CIRCUM REBAR
19.2SRCBROKEN REBAR CIRCUM
335.9MGO60% MISSING TILES
156.8MWM
0MWL
442.8AMH5:25AM
258.1SRCLONG & CIRCUM REBAR
442.4SRCBROKEN MISSING REBAR
442.4MGOConn. @ Mh, 12 O' Clock. OPEN
149.1SRCCORRISON BEYOUND REBAR
442.4SRCCORRISON BEYOUND REBAR
0AMH4:30AM
368.7MWL
133.6SRCBROKEN REBAR
122MGO2 ROWS TILES
316.3SRCBROKEN MISSING REBAR
102.3MGOMISSING TILES 100% START
316.3MGO100% MISSING TILES
115.7MGO3 ROWS TILES
156.8MWL
208.1MGO10% MISSING TILES

Properties (4)

custom_field_three
CORRISON BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2018-12-12T04:25:24-08:00