08 0006_08 0005_12112018_013129.mp4
2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG
2 ft. - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
3.5 ft. - Hole Void Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - SOIL VISIBLE
3.5 ft. - Hole Void Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - SLIGHTLY DEEPER VOID
5.6 ft. - Hole Void Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - LARGER AREA OF SOIL
5.6 ft. - Hole Void Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - SLIGHTLY DEEPER VOID FINISH
5.6 ft. - Hole Soil Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - LARGER AREA OF SOIL
7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR
13.1 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR
27.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR
65.5 ft. - Surface Reinforcement Corroded, at 03 o'clock, within 8 inches of joint: NO - MISSING REBAR
86.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR
114.1 ft. - General Observation - DEEP CORRISON
114.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR HANGING
125.5 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR
| Distance | Code | Observation |
|---|---|---|
| 5.6 | HVV | LARGER AREA OF SOIL |
| 2 | MGO | MISSING TILES 100% START |
| 0 | MWM | — |
| 86.2 | SRC | LONG & CIRCUM REBAR |
| 262.3 | SAM | SEVERE AGG |
| 125.5 | SRC | CORRISON BEYOUND REBAR |
| 27.7 | SRC | LONG & CIRCUM REBAR |
| 264.8 | AMH | 2:10AM |
| 264.2 | SRC | MISSING BROKEN REBAR |
| 3.5 | HVV | SOIL VISIBLE |
| 5.6 | HVV | SLIGHTLY DEEPER VOID FINISH |
| 13.1 | SRC | LONG REBAR |
| 2 | SAM | SEVERE AGG |
| 3.5 | HVV | SLIGHTLY DEEPER VOID |
| 114.1 | MGO | DEEP CORRISON |
| 114.1 | SRC | BROKEN REBAR HANGING |
| 1 | DAGS | INSIDE MH |
| 65.5 | SRC | MISSING REBAR |
| 2 | SRV | CIRCUM REBAR |
| 5.6 | HSV | LARGER AREA OF SOIL |
| 7 | SRC | LONG & CIRCUM REBAR |
| 0 | MWL | — |
| 0 | AMH | 1:20AM |
| 0 | MGO | Conn. @ Mh, 3 O' Clock. Active |