B 1501_B 1500 _11282016_034002.mp4
2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start
252.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES
304.4 ft. - Hole Void Visible, from 08 to 04 o'clock, within 8 inches of joint: YES
346.6 ft. - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 08 to 09 o'clock
542.1 ft. - Hole Void Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start
542.1 ft. - Roots Medium Joint, from 02 to 05 o'clock, 20 %, within 8 inches of joint: YESR
568.3 ft. - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 03 to 04 o'clock
608.5 ft. - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 09 to 10 o'clock
620.9 ft. - Broken Soil Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - COULD JUST BE SPALLING
| Distance | Code | Observation |
|---|---|---|
| 0 | MWL | — |
| 2 | SSS | — |
| 625.8 | AMH | B 1500 |
| 542.1 | HVV | — |
| 252.2 | DAE | — |
| 608.5 | ISSRH | — |
| 620.9 | DAGS | — |
| 346.6 | ISSRH | — |
| 2.7 | DAGS | — |
| 568.3 | ISSRH | — |
| 542.1 | RMJ | — |
| 0 | MWM | — |
| 621 | SSS | — |
| 0 | AMH | B 1501 |
| 304.4 | HVV | — |
| 546.2 | HVV | — |
| 620.9 | BSV | COULD JUST BE SPALLING |