Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2016, 07:23 AM
  • B 1518_B 1517 _11282016_233619.mp4

Date
11/28/2016
W/O
608085
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z01124
PipeID
P25632
Time
11:23 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3888
Sewer Name
B JOINT OUTFALL B - UNIT 6G
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
23
Purpose
Routine Assessment
Project
WO_608085_TV16038_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
B 1518
Downstream MH
B 1517
Dir. of Survey
Downstream
Length Surveyed
213.6 ft.
Total Length
213.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2G12
O&M Rating
86
Overall Index
2
Overall Quick
Overall Rating
86
Pipe schematic from manhole B 1518 to B 1517
MH: B 1518MH: B 1517downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Begins - B 15182.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start209.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish209.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish213.7 ft. VC - Vermin Cockroach213.7 ft. AMH - Downstream Manhole, Survey Ends - B 1517

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
209.1DAE
0MWM
213.7VC
0MWL
2.8DAE
0VC
209.1DAGS
0AMHB 1518
2.8DAGS
213.7AMHB 1517

Properties (7)

additional_info
SC305222
custom_field_two
4
customer
LACSD
datetime
2016-11-28T23:23:30-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
38886