Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2016, 05:44 AM
  • 14 0164_14 0163A_09202016_223823.mp4

Date
09/20/2016
W/O
592016
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P23489
Time
10:44 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3765
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
17
Purpose
Routine Assessment
Project
WO_592016_TV14035_SEP2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0164
Downstream MH
14 0163A
Dir. of Survey
Downstream
Length Surveyed
110.2 ft.
Total Length
110.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 14 0164 to 14 0163A
MH: 14 0164MH: 14 0163Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 01640 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start14.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"17.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"70 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish109.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish110.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK110.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0163A110.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    110.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
2DAGS
70TFC
110.2MGOACTIVE CONNECTION AT MH 9 O'CLOCK
66.5TFC
0AMH14 0164
2SAV
109.2SAV
110.2AMH14 0163A
17.8TFC
14.1TFC
0MWM
109.2DAGS
110.2MGOCOCKROACHES IN MANHOLE
0MWL

Properties (6)

additional_info
SC302758
custom_field_two
3
customer
LACSD
datetime
2016-09-20T22:44:17-07:00
documentation
PRO PIPE
is_lateral_inspection
false