Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2016, 06:40 AM
  • 14 0163_14 0162B_09212016_235006.mp4

Date
09/20/2016
W/O
592016
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18201
Time
11:40 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3765
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
17
Purpose
Routine Assessment
Project
WO_592016_TV14035_SEP2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0163
Downstream MH
14 0162B
Dir. of Survey
Downstream
Length Surveyed
177.4 ft.
Total Length
177.4 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
105
O&M Index
2
O&M Quick
412F
O&M Rating
74
Overall Index
3
Overall Quick
Overall Rating
179
Pipe schematic from manhole 14 0163 to 14 0162B
MH: 14 0163MH: 14 0162Bdownstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 14 01630 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CAPPED CONNECTION AT 3 OCLOCK0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start19.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"65.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"116.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"165 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"175.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish175.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish177.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK177.4 ft. AMH - Downstream Manhole, Survey Ends - 14 0162B

Observation photos (2)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
116.2TFC
177.4MGOACTIVE CONNECTION AT MH 9 O'CLOCK
119.7TFC
0AMH14 0163
2SAV
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
65.4TFC
175.4DAGS
0MGOCAPPED CONNECTION AT 3 OCLOCK
165TFC
175.4SAV
0MWL
2DAGS
19.3TFC
168.4TFC
0MWM
68.2TFC
177.4AMH14 0162B

Properties (6)

additional_info
SC302758
custom_field_two
3
customer
LACSD
datetime
2016-09-20T23:40:20-07:00
documentation
PRO PIPE
is_lateral_inspection
false