Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2016, 10:34 AM
  • 14 0160_14 0159_09212016_034515.mp4

Date
09/21/2016
W/O
592016
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18196
Time
3:34 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3765
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_592016_TV14035_SEP2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0159
Downstream MH
14 0160
Dir. of Survey
Upstream
Length Surveyed
445.8 ft.
Total Length
445.8 ft.
Structural Index
3
Structural Quick
3Q2Q
Structural Rating
445
O&M Index
2
O&M Quick
412Q
O&M Rating
182
Overall Index
2
Overall Quick
Overall Rating
627
Pipe schematic from manhole 14 0159 to 14 0160
MH: 14 0159MH: 14 0160upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 12 O'CLOCK0 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish0 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 1 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 14 01600 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish55.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"211.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"259.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"263.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"311.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"359.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"363.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"411.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"415.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"443.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start443.8 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start443.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start445.8 ft. AMH - Downstream Manhole, Survey Begins - 14 0159445.8 ft. MWM - Water Mark, 65 %of cross sectional area445.8 ft. MWL - Water Level, 50 %of cross sectional area

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    133.9 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (28)

DistanceCodeObservation
445.8MGOACTIVE CONNECTION AT MH 12 O'CLOCK
0AMH14 0159
136.4TFC
234.2TFC
2DAGS
186TFC
445.8SAV
0MWM
337.6TFC
285.6TFC
34TFC
2SSS
390.5TFC
445.8SSS
2SAV
386.8TFC
182.5TFC
0MWL
283.1TFC
445.8MGOACTIVE CONNECTION AT MH 1 O'CLOCK
85.9TFC
133.9TFA
82.2TFC
445.8AMH14 0160
445.8DAGS
30.2TFA
236.6TFC
335.1TFA

Properties (6)

additional_info
SC302758
custom_field_two
2
customer
LACSD
datetime
2016-09-21T03:34:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false