Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 25, 2016, 09:25 AM
  • 14 0170_14 0169_10252016_003131.mp4

Date
10/25/2016
W/O
592016
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18208
Time
2:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3792
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
17
Purpose
V
Project
WO_592016_TV14035_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0170
Downstream MH
14 0169
Dir. of Survey
Downstream
Length Surveyed
6.1 ft.
Total Length
6.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4131
O&M Rating
11
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 14 0170 to 14 0169
MH: 14 0170MH: 14 0169downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 01702 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES6.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"6.1 ft. MSA - Survey Abandoned - DUE TO DEBRIS/DEPOSITS6.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  15 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    4.5 ft. - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
4.5DSZ
6.1TFC
0MWM
6.1MSADUE TO DEBRIS/DEPOSITS
0MWL
6.1DAGS
2DAGS
0AMH14 0170

Properties (6)

additional_info
SC302757
custom_field_two
5
customer
LACSD
datetime
2016-10-25T02:25:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false