Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2018, 11:39 AM
  • 22 0469_22 0468_142018_035557.mp4

Date
01/04/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00816
PipeID
P16807
Time
3:39 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0720
Sewer Name
22 LARK ELLEN TRUNK, SECTS 4,5,&6
City
IRWINDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20180104MDM_LARK_ELLEN_TRUNK_SECTS_4_5_6
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0469
Downstream MH
22 0468
Dir. of Survey
Downstream
Length Surveyed
278.7 ft.
Total Length
278.7 ft.
Structural Index
3
Structural Quick
4221
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 22 0469 to 22 0468
MH: 22 0469MH: 22 0468downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0 ft. AMH - Upstream Manhole, Survey Begins - 3:55AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTCHED2 ft. MGO - General Observation - MAG COAT 60% START 9:00 TO 3:002 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG58.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open68.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Active119.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open126.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG192.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open197.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active261.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open278.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG278.1 ft. MGO - General Observation - MAG COAT 60% FINISH278.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED278.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN278.7 ft. AMH - Downstream Manhole, Survey Ends - 4:15AM

Observation photos (4)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTCHED

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTCHED

  • General Observation - MAG COAT 60% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 60% START 9:00 TO 3:00

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    126.6 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (20)

DistanceCodeObservation
0MGOConn. @ Mh, 3 O' Clock. Capped
68.1TFActive
0AMH3:55AM
2SSSPEELING CONCRETE SEVERE AGG ATTCHED
278.1SAMSEVERE AGG
261.5TFOpen
278.7AMH4:15AM
197.7TFActive
119.3TFOpen
2MGOMAG COAT 60% START 9:00 TO 3:00
0MGOConn. @ Mh, 9 O' Clock. Active
126.6SAMSEVERE AGG
192.5TFOpen
278.1MGOMAG COAT 60% FINISH
2SAMSEVERE AGG
278.1SSSPEELING CONCRETE SEVERE AGG ATTACHED
0MWL
278.1MGOConn. @ Mh, 9 O' Clock. OPEN
58.7TFOpen
0MWM

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTCHED
custom_field_two
2
customer
LACSD
datetime
2018-01-04T03:39:35-08:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection
false