Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2017, 08:35 AM
Date
09/29/2017
W/O
663060
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13593
Time
1:35 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4281
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
15
Purpose
Routine Assessment
Project
WO_630370_TV05315_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
16 0542
Downstream MH
16 0541
Dir. of Survey
Downstream
Length Surveyed
225.2 ft.
Total Length
225.2 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
132
O&M Index
2
O&M Quick
2H12
O&M Rating
90
Overall Index
2
Overall Quick
Overall Rating
222
Pipe schematic from manhole 16 0542 to 16 0541
MH: 16 0542MH: 16 0541downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05420.1 ft. MWM - Water Mark, 15 %of cross sectional area0.1 ft. VC - Vermin Cockroach0.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. MGO - General Observation - MAG COAT START2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"76.6 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"132.6 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"180.8 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"186.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"220.8 ft. MGO - General Observation - MAG COAT FINISH220.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish220.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish225.2 ft. AMH - Downstream Manhole, Survey Ends - 16 0541225.2 ft. VC - Vermin Cockroach

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
225.2AMH16 0541
2.4DAGS
220.8MGOMAG COAT FINISH
0.1MWM
0.1VC
28TFA
76.6TBA
225.2VC
0MWL
0.1MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
2.4MGOMAG COAT START
180.8TBA
220.8DAGS
2.4SAV
0AMH16 0542
132.6TBA
220.8SAV
186.4TFC

Properties (5)

additional_info
SC352127
custom_field_two
3
customer
LACSD
datetime
2017-09-29T01:35:00-07:00
is_lateral_inspection
false