Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2017, 09:24 AM
Date
09/29/2017
W/O
663060
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13591
Time
2:24 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4281
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
15
Purpose
Routine Assessment
Project
WO_630370_TV05315_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
16 0539
Downstream MH
16 0540
Dir. of Survey
Upstream
Length Surveyed
217.2 ft.
Total Length
217.2 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
129
O&M Index
2
O&M Quick
2H12
O&M Rating
88
Overall Index
2
Overall Quick
Overall Rating
217
Pipe schematic from manhole 16 0539 to 16 0540
MH: 16 0539MH: 16 0540upstream0 ft. AMH - Upstream Manhole, Survey Ends - 16 05400 ft. VC - Vermin Cockroach1.8 ft. MGO - General Observation - MAG COAT FINISH1.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish6.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"16.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"59.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"63.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"86.9 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"91.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"115.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"165.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"171.3 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4"192.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"215.1 ft. MGO - General Observation - MAG COAT START215.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start215.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start217.2 ft. VC - Vermin Cockroach217.2 ft. MWL - Water Level, 5 %of cross sectional area217.2 ft. MWM - Water Mark, 15 %of cross sectional area217.2 ft. AMH - Downstream Manhole, Survey Begins - 16 0539217.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
200.5TBA
2.1MGOMAG COAT START
2.1DAGS
214.7DAGS
0VC
45.9TB
217.2AMH16 0540
217.2VC
24.8TFC
157.5TFC
51.7TFC
153.7TFC
125.4TFC
0MWL
0MWM
0AMH16 0539
210.3TFC
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
2.1SAV
130.3TBA
215.4MGOMAG COAT FINISH
101.8TFC
215.4SAV

Properties (5)

additional_info
SC352127
custom_field_two
3
customer
LACSD
datetime
2017-09-29T02:24:05-07:00
is_lateral_inspection
false