08 0172_08 0171_29092017_024352.mp4
2.1 ft. - Deposits Settled Other, 10 %of cross sectional area, from 04 to 06 o'clock, , within 8 inches of joint: NO
4.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start
59.6 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES
63.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES
74.4 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES
81.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES
86.6 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES
94.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start
| Distance | Code | Observation |
|---|---|---|
| 330.4 | CM | — |
| 59.6 | CL | — |
| 0 | MWL | — |
| 0 | MGO | CONNECTION AT MH 3 O'CLOCK |
| 4.1 | DAGS | — |
| 74.4 | CL | — |
| 220.3 | TF | — |
| 2.1 | DSZ | — |
| 81.7 | CL | — |
| 314.3 | TFA | — |
| 136.2 | TF | — |
| 63.5 | CM | — |
| 86.6 | CL | — |
| 330.4 | DAGS | — |
| 98 | TF | — |
| 271.5 | TF | — |
| 0 | AMH | 08 0172 |
| 0 | MGO | CONNECTION AT MH 9 O'CLOCK |
| 94.6 | CM | — |
| 67.8 | TFA | — |
| 0 | MWM | — |
| 329 | MGO | SPALLING THROUGHOUT THE REACH |
| 184.8 | TF | — |
| 330.4 | AMH | 08 0171 |