Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 12, 2017, 09:06 AM
Date
09/12/2017
W/O
657840
Weather
Dry
Operator/Surveyor
CORTEZ ESTEBAN
Sewer ID
Z00199
PipeID
P01388
Time
2:06 AM
Certificate
U-209-848
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4922
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
14
Purpose
Routine Assessment
Project
WO_630370_TV05315_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
01 0679
Downstream MH
01 0678
Dir. of Survey
Downstream
Length Surveyed
350.9 ft.
Total Length
350.9 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 01 0679 to 01 0678
MH: 01 0679MH: 01 0678downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 06790 ft. MWM - Water Mark, 30 %of cross sectional area2.9 ft. MGO - General Observation - MAGNEZIUM H.O COATING start2.9 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start125.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"168.5 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"226.4 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"346.4 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish347.3 ft. MGO - General Observation - MAGNEZIUM H.O COATING finish349 ft. MGO - General Observation - PEELING/FLAKING/SPALLING THROUGHOUT THE REACH350.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0678

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
125.8TFA
350.9AMH01 0678
226.4TB
2.9MGOMAGNEZIUM H.O COATING start
346.4SAV
2.9SAV
349MGOPEELING/FLAKING/SPALLING THROUGHOUT THE REACH
0MWL
0AMH01 0679
168.5TBA
0MWM
347.3MGOMAGNEZIUM H.O COATING finish

Properties (5)

additional_info
SC345829
custom_field_two
3
customer
LACSD
datetime
2017-09-12T02:06:00-07:00
is_lateral_inspection
false