Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 19, 2017, 06:37 AM
  • 14 0208_14 0207 _09182017_233817.mp4

Date
09/18/2017
W/O
657830
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18247
Time
11:37 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4728
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_657830_TV14033_SEP2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
14 0208
Downstream MH
14 0207
Dir. of Survey
Downstream
Length Surveyed
302.2 ft.
Total Length
302.2 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
301
Pipe schematic from manhole 14 0208 to 14 0207
MH: 14 0208MH: 14 0207downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 02082 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.1 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES11.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS21.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"79.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"81.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"138.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"141.4 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"198.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"201 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"258.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS261.2 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"300.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish300.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish302.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0207

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    8.1 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

    19 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

    258.3 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

Observations (19)

DistanceCodeObservation
0MWM
0MWL
11.3CM
81.5TFA
258.3TFDROOTS
201TFA
141.4TFA
138.7TFA
198.2TFA
21.8TFA
300.5DAGS
19TFDROOTS
261.2TFA
302.2AMH14 0207
79.1TFA
8.1CM
300.5CM
2DAGS
0AMH14 0208

Properties (5)

additional_info
SC345741
custom_field_two
3
customer
LACSD
datetime
2017-09-18T23:37:33-07:00
is_lateral_inspection
false