Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 20, 2017, 04:48 AM
  • 32 1167_32 1166_19092017_215912.mp4

Date
09/19/2017
W/O
654216
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00839
PipeID
P19621
Time
9:48 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4881
Sewer Name
32 SAN FERNANDO ROAD TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_630370_TV05315_AUG2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1167
Downstream MH
32 1166
Dir. of Survey
Downstream
Length Surveyed
114.4 ft.
Total Length
114.4 ft.
Structural Index
2
Structural Quick
322C
Structural Rating
50
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
50
Pipe schematic from manhole 32 1167 to 32 1166
MH: 32 1167MH: 32 1166downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 11672 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start101.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"113 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish114.3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish114.4 ft. AMH - Downstream Manhole, Survey Ends - 32 1166

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2SSS
114.3SAV
0MWM
113SSS
101.7TFC
0MWL
2.1SAV
114.4AMH32 1166
0AMH32 1167

Properties (5)

additional_info
SC345941
custom_field_two
2
customer
LACSD
datetime
2017-09-19T21:48:25-07:00
is_lateral_inspection
false