Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 6, 2016, 12:27 PM
  • 02 1544A_02 1544_12062016_043400.mp4

Date
12/06/2016
W/O
607654
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00230
PipeID
P03973
Time
4:27 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3932
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
EAST LOS ANGELES
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_607654_TV02006_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1544A
Downstream MH
02 1544
Dir. of Survey
Downstream
Length Surveyed
191.6 ft.
Total Length
191.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 1544A to 02 1544
MH: 02 1544AMH: 02 1544downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 1544A0 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK0 ft. VC - Vermin Cockroach2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start97.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"110 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"149.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"179.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"189.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish191.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1544

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
0MWM
179.3TBA
0AMH02 1544A
149.4TB
97.2TB
189.2DAGS
2DAGS
110TBA
191.6AMH02 1544
0MGOLATERAL AT MH 9 O CLOCK
0VC

Properties (6)

additional_info
SC307676
custom_field_two
4
customer
LACSD
datetime
2016-12-06T04:27:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false