Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2016, 09:25 AM
  • 02 1276_02 1275A_12092016_013729.mp4

Date
12/09/2016
W/O
607634
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00238
PipeID
P03790
Time
1:25 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3936
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_607634_TV02329_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 1276
Downstream MH
02 1275A
Dir. of Survey
Downstream
Length Surveyed
199.7 ft.
Total Length
199.7 ft.
Structural Index
3
Structural Quick
5122
Structural Rating
9
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 02 1276 to 02 1275A
MH: 02 1276MH: 02 1275Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12763.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start132.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start147.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish154.6 ft. B - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES197.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish199.7 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK199.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1275A

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    132.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

    154.6 ft. - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
197.5DAGS
199.7MGOLATERAL AT MH 9 O CLOCK
147.3CL
0MWM
0MWL
3.1DAGS
132.9CL
199.7AMH02 1275A
0AMH02 1276
154.6B

Properties (6)

additional_info
SC317680
custom_field_two
2
customer
LACSD
datetime
2016-12-09T01:25:35-08:00
documentation
PRO-PIPE
is_lateral_inspection
false