Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2016, 10:04 AM
  • 02 1274_02 1273_12092016_021421.mp4

Date
12/09/2016
W/O
607634
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00238
PipeID
P03787
Time
2:04 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3936
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_607634_TV02329_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 1274
Downstream MH
02 1273
Dir. of Survey
Downstream
Length Surveyed
325.9 ft.
Total Length
325.9 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 1274 to 02 1273
MH: 02 1274MH: 02 1273downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12740 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start48 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start123.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish206.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"322.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish325.9 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK325.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1273

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    48 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
325.9MGOLATERAL AT MH 9 O CLOCK
0MWL
2.2DAGS
48CL
206.6TF
0MWM
123.9CL
0AMH02 1274
322.2DAGS
0MGOLATERAL AT MH 9 O CLOCK
325.9AMH02 1273

Properties (6)

additional_info
SC317680
custom_field_two
3
customer
LACSD
datetime
2016-12-09T02:04:11-08:00
documentation
PRO-PIPE
is_lateral_inspection
false