Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2016, 07:12 AM
  • 02 1289_02 1288_12082016_232332.mp4

Date
12/08/2016
W/O
607634
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00238
PipeID
P03806
Time
11:12 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3936
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_607634_TV02329_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 1289
Downstream MH
02 1288
Dir. of Survey
Downstream
Length Surveyed
309.2 ft.
Total Length
309.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 1289 to 02 1288
MH: 02 1289MH: 02 1288downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 12890 ft. MWL - Water Level, 15 %of cross sectional area3.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start61.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish166.9 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"304.5 ft. CM - Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: NO308.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish309.2 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK309.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1288

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: NO

    304.5 ft. - Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: NO

Observations (12)

DistanceCodeObservation
0MWM
0MGOLATERAL AT MH 9 O CLOCK
61.6CM
3.9DAGS
308.5DAGS
309.2MGOLATERAL AT MH 9 O CLOCK
309.2AMH02 1288
3.9CM
304.5CM
0AMH02 1289
166.9TBA
0MWL

Properties (6)

additional_info
SC317680
custom_field_two
3
customer
LACSD
datetime
2016-12-08T23:12:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false