Wastewater/Activity/PacpInspection/1.0Nov 7, 2016, 11:20 AM
  • 22 0355_22 0354 _11072016_032242.mp4

Date
11/07/2016
W/O
602235
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00830
PipeID
P16687
Time
3:20 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4006
Sewer Name
22 WALNUT CREEK TRUNK, SECTS 1&2
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
32
Purpose
Routine Assessment
Project
WO_602235_TV22111_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0355
Downstream MH
22 0354
Dir. of Survey
Downstream
Length Surveyed
435.6 ft.
Total Length
435.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412P
O&M Rating
176
Overall Index
2
Overall Quick
Overall Rating
176
Pipe schematic from manhole 22 0355 to 22 0354
MH: 22 0355MH: 22 0354downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 03550 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start43.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"93.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"144.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"194.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"244.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"294.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"345.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"390.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"433.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish435.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0354

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
294.2TFC
435.6AMH22 0354
433.8DAGS
0AMH22 0355
345.4TFC
43.5TFC
251.4TFA
93.7TFC
2DAGS
244.4TFC
144.3TF
0MWM
194.3TFC
390.7TFC
0MWL

Properties (6)

additional_info
SC306346
custom_field_two
4
customer
LACSD
datetime
2016-11-07T03:20:59-08:00
documentation
PRO PIPE
is_lateral_inspection
false