Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2016, 09:52 AM
  • 01 0527A_01 0527_12052016_021214.mp4

Date
12/05/2016
W/O
602233
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00206
PipeID
P01014
Time
1:52 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3896
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_602233_TV01017_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0527
Downstream MH
01 0527A
Dir. of Survey
Upstream
Length Surveyed
342 ft.
Total Length
343.9 ft.
Structural Index
3
Structural Quick
4121
Structural Rating
6
O&M Index
2
O&M Quick
322M
O&M Rating
146
Overall Index
2
Overall Quick
Overall Rating
152
Pipe schematic from manhole 01 0527 to 01 0527A
MH: 01 0527MH: 01 0527Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 0527A0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE0 ft. VC - Vermin Cockroach - AT MH3.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish84.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"87.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"114 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area144 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"147.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"185.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"224.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"226.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"272.3 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 08 o'clock - DEBRIS NOT VISIBLE275.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"278.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"286.5 ft. OBZ - Obstacles Other, 15 %of cross sectional area, from 04 to 08 o'clock - DEBRIS NOT VISIBLE339.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES339.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start342 ft. VC - Vermin Cockroach - AT MH342 ft. MWM - Water Mark, 15 %of cross sectional area342 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE342 ft. MWL - Water Level, 10 %of cross sectional area342 ft. AMH - Downstream Manhole, Survey Begins - 01 0527

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Water Level, Sag in pipe, 15 %of cross sectional area

    228 ft. - Water Level, Sag in pipe, 15 %of cross sectional area

Observations (23)

DistanceCodeObservation
2.5FM
55.5OBZDEBRIS NOT VISIBLE
0VCAT MH
254.1TFC
115.6TFC
117.6TFC
194.9TFC
342AMH01 0527A
257.2TFC
0MWM
342MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
342VCAT MH
338.6DAGS
66.4TFC
69.7OBZDEBRIS NOT VISIBLE
228MWLS
2.1DAGS
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
156.3TFC
0MWL
0AMH01 0527
63.5TFC
198TFC

Properties (6)

additional_info
SC305230
custom_field_two
4
customer
LACSD
datetime
2016-12-05T01:52:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false