Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2016, 10:35 AM
  • 01 0527_01 0526A_12052016_024754.mp4

Date
12/05/2016
W/O
602233
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00206
PipeID
P01013
Time
2:35 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3896
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_602233_TV01017_DEC2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0527
Downstream MH
01 0526A
Dir. of Survey
Downstream
Length Surveyed
211.7 ft.
Total Length
211.7 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2G11
O&M Rating
85
Overall Index
2
Overall Quick
Overall Rating
91
Pipe schematic from manhole 01 0527 to 01 0526A
MH: 01 0527MH: 01 0526Adownstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 05270 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start20.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish76.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"78.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"127.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"129.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"177.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"180.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"209.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish211.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE211.7 ft. MGO - General Observation - PIECE OF WOOD AT MH211.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0526A

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0MWM
2.1DAGS
180.2TFC
78.7TFC
9FL
211.7MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
0MWL
209.9DAGS
211.7MGOPIECE OF WOOD AT MH
127.4TFC
0VCAT MH
0AMH01 0527
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
211.7AMH01 0526A
129.7TFC
76.4TFC
177.5TFC
20.3FL

Properties (6)

additional_info
SC305230
custom_field_two
3
customer
LACSD
datetime
2016-12-05T02:35:12-08:00
documentation
PRO PIPE
is_lateral_inspection
false