Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2016, 05:27 AM
  • 14 0117_14 0116A _09152016_222843.mp4

Date
09/15/2016
W/O
592238
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00571
PipeID
P25683
Time
10:27 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3760
Sewer Name
14 DISTRICT #14 OUTFALL TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
WO_592238_TV14075_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0117
Downstream MH
14 0116A
Dir. of Survey
Downstream
Length Surveyed
410.6 ft.
Total Length
410.6 ft.
Structural Index
3
Structural Quick
443C
Structural Rating
75
O&M Index
2
O&M Quick
412Q
O&M Rating
188
Overall Index
2
Overall Quick
Overall Rating
263
Pipe schematic from manhole 14 0117 to 14 0116A
MH: 14 0117MH: 14 0116Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 01170 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.9 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"96.1 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"100.1 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"150.1 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"212.8 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"247.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start257.8 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"268.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES272.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES288.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start304.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish311.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish341.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES345.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start359.9 ft. MWL - Water Level, 40 %of cross sectional area361.4 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES364.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"365.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start381.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish405.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish409.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish410.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK410.6 ft. AMH - Downstream Manhole, Survey Ends - 14 0116A

Observation photos (9)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    247.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    268.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    272.8 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    288.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    341.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    345.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    361.4 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    365.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
272.8CL
96.1TBA
0AMH14 0117
0MWM
409.3DAGS
150.1TBA
100.1TBA
212.8TBA
405.9CM
247.1DAE
341.5CM
365.9FM
304.3DAE
345.4CM
257.8TBA
410.5MGOACTIVE CONNECTION AT MH 9 O'CLOCK
268.4CM
364.9TBA
288.4CM
410.6AMH14 0116A
8.9TBA
0MWL
359.9MWL
2DAGS
311.9CM
361.4FM
381.6FM