Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2016, 09:00 AM
  • 05 1499_05 1498_19102016_020215.mp4

Date
10/19/2016
W/O
592160
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00497
PipeID
P06722
Time
2:00 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3809
Sewer Name
05 NORTH TORRANCE EXTENSION TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
26
Purpose
Routine Assessment
Project
WO_592160_TV05263_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 1499
Downstream MH
05 1498
Dir. of Survey
Downstream
Length Surveyed
350.9 ft.
Total Length
350.9 ft.
Structural Index
2
Structural Quick
2411
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 05 1499 to 05 1498
MH: 05 1499MH: 05 1498downstream0 ft. MGO - General Observation - FLOW METER0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 149923.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"42.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"48.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES60.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES83.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.3 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES112.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"135.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"205.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"215.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"295.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"310.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"334.6 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES339.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES350.9 ft. AMH - Downstream Manhole, Survey Ends - 05 1498

Observation photos (8)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    48.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    71.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    83.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    100.3 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    215.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    295.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES

    334.6 ft. - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    339.8 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
93.6TFC
0MGOFLOW METER
135.5TF
350.9AMH05 1498
60.5TF
172.1TF
205.7TF
42.2TF
246.7TF
83.9TB
0MWL
48.4CL
310.6TF
100.3CL
0MWM
334.6CC
71.7CL
0AMH05 1499
215.6TB
23.8TF
168.7TFC
205.9TF
112.2TF
244.2TFC
339.8CL
295.8TB

Properties (6)

additional_info
SC304554
custom_field_two
4
customer
LACSD
datetime
2016-10-19T02:00:14-07:00
documentation
PROPIPE
is_lateral_inspection
false