Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 9, 2017, 08:34 AM
  • 03 0435_03 0434_692017_014613.mp4

Date
06/09/2017
W/O
0630066
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00406
PipeID
P04983
Time
1:34 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0557
Sewer Name
03 WATER STREET TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
22
Purpose
Routine Assessment
Project
20170609MDM_WATER_STREET_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
03 0435
Downstream MH
03 0434
Dir. of Survey
Downstream
Length Surveyed
66.6 ft.
Total Length
66.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 03 0435 to 03 0434
MH: 03 0435MH: 03 0434downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 1:35AM0 ft. MWM - Water Mark, 20 %of cross sectional area8 ft. MGO - General Observation - 26" RCP-PVC SPIRAL LINER42.3 ft. MGP - General Photograph56.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - SLUDGE66.6 ft. AMH - Upstream Manhole, Survey Ends - 1:50AM

Observation photos (2)

  • General Observation - 26" RCP-PVC SPIRAL LINER

    8 ft. - General Observation - 26" RCP-PVC SPIRAL LINER

  • General Photograph

    42.3 ft. - General Photograph

Observations (8)

DistanceCodeObservation
0MWL
0MGOConn. @ Mh, 9 O' Clock. Active
42.3MGP
8MGO26" RCP-PVC SPIRAL LINER
0AMH1:35AM
0MWM
66.6AMH1:50AM
56.5DSZSLUDGE

Properties (6)

custom_field_three
LINER GOOD COND.
custom_field_two
4
customer
LACSD
datetime
2017-06-09T01:34:34-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false