Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 30, 2016, 06:58 AM
  • 22 0863_22 0862 _09292016_235806.mp4

Date
09/29/2016
W/O
596657
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00803
PipeID
P17230
Time
11:58 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3723
Sewer Name
22 DALTON TRUNK, SECTION 3
City
AZUSA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
WO_596657_TV599657_OCT2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
22 0863
Downstream MH
22 0862
Dir. of Survey
Downstream
Length Surveyed
374.4 ft.
Total Length
374.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
148
Pipe schematic from manhole 22 0863 to 22 0862
MH: 22 0863MH: 22 0862downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 08630 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start2 ft. MGO - General Observation - MAG. H.OX START 80%28.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"36.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"83.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"85.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"140.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"141 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"183.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"198.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"231.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"272.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"281 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"371.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish374.4 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE374.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0862

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

Observations (19)

DistanceCodeObservation
2DAGS
198.1TFA
281TFA
0AMH22 0863
28.3TFC
371.8DAGS
2MGOMAG. H.OX START 80%
140.1TFC
374.4MGOCONNECTION AT MH 3 ACTIVE
0MWM
0MWL
231.2TFC
183.4TFA
374.4AMH22 0862
141TFA
272.4TFA
83.7TFA
85.5TFA
36.4TFA

Properties (6)

additional_info
SC303710
custom_field_two
5
customer
LACSD
datetime
2016-09-29T23:58:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false