Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 26, 2018, 08:08 AM
  • D 0102_D 0101_4262018_020150.mp4

Date
04/26/2018
W/O
0703211
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00156
PipeID
P10008
Time
1:08 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0843
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
LAWDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20180426MDM_JOINT_OUTFALL_D_UNIT_6
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Upstream MH
D 0102
Downstream MH
D 0101
Dir. of Survey
Downstream
Length Surveyed
500.5 ft.
Total Length
500.5 ft.
Structural Index
4
Structural Quick
5A33
Structural Rating
75
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
75
Pipe schematic from manhole D 0102 to D 0101
MH: D 0102MH: D 0101downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:50AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING PEELING CONCRETE9.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG10.4 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR14.6 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR22 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG22 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC46.2 ft. MGO - General Observation - 25% MAG COAT START68.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE86.9 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR87.8 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE97.1 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR103 ft. MGO - General Observation - 60% MAG COAT START167 ft. SAP - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG257 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CURCUM REBAR264.9 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR266 ft. MGO - General Observation - 60% MAG COAT FINISH301.3 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR307.6 ft. SRV - Surface Reinforcement Visible, from 10 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR312 ft. SRV - Surface Reinforcement Visible, from 10 to 03 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR336.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, - CFIRCUM REBAR382.4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR446.2 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR469.6 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR500.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SWOLLEN BLISTERING PEELING CONCRETE500.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG500.5 ft. AMH - Downstream Manhole, Survey Ends - 2:50AM

Observation photos (21)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    9.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    10.4 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    14.6 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    22 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • General Observation - 25% MAG COAT START

    46.2 ft. - General Observation - 25% MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    68.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    86.9 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    87.8 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    97.1 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - 60% MAG COAT START

    103 ft. - General Observation - 60% MAG COAT START

  • Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    167 ft. - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CURCUM REBAR

    257 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CURCUM REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    264.9 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - 60% MAG COAT FINISH

    266 ft. - General Observation - 60% MAG COAT FINISH

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    301.3 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    307.6 ft. - Surface Reinforcement Visible, from 10 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES,  - CFIRCUM REBAR

    336.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, - CFIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    382.4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    446.2 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    469.6 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

Observations (29)

DistanceCodeObservation
301.3SRVCIRCUM REBAR
103MGO60% MAG COAT START
500.2SSSSWOLLEN BLISTERING PEELING CONCRETE
382.4SRVCIRCUM REBAR
2SSSSWOLLEN BLISTERING PEELING CONCRETE
97.1SRVCIRCUM REBAR
86.9SRVCIRCUM REBAR
87.8SSSPEELING CONCRETE
307.6SRVCIRCUM REBAR
336.3SRVCFIRCUM REBAR
266MGO60% MAG COAT FINISH
500.5AMH2:50AM
46.2MGO25% MAG COAT START
500.2SAVSEVERE AGG
14.6SRVCIRCUM REBAR
167SAPSEVERE AGG
68.5SSSPEELING CONCRETE
469.6SRVCIRCUM REBAR
10.4SRVCIRCUM REBAR
22SAVSEVERE AGG
257SRVCURCUM REBAR
0MWM
0AMH1:50AM
22SAVSEVERE AGG SPORATIC
264.9SRVCIRCUM REBAR
446.2SRVCIRCUM REBAR
312SRVCIRCUM REBAR
0MWL
9.3SAVSEVERE AGG

Properties (6)

custom_field_three
VISIBLE CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2018-04-26T01:08:06-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false