Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 25, 2018, 08:29 AM
  • J 0358_J 0357_4252018_022934.mp4

Date
04/25/2018
W/O
0701115
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00070
PipeID
P11722
Time
1:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0841
Sewer Name
J JOINT OUTFALL J - UNIT 5C
City
HOLLYWOOD RIVIERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
20180425MDM_JOINT_OUTFALL_J_UNIT_5C
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
J 0358
Downstream MH
J 0357
Dir. of Survey
Downstream
Length Surveyed
194.5 ft.
Total Length
194.5 ft.
Structural Index
2
Structural Quick
3B2A
Structural Rating
78
O&M Index
2
O&M Quick
3121
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
85
Pipe schematic from manhole J 0358 to J 0357
MH: J 0358MH: J 0357downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active-OUTGOING LINE0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active9 ft. MGO - General Observation - 8" VCP15 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H15 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE38.9 ft. JOM - Joint Offset Medium53.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H55.5 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H58 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: NO - SLIGHT58.6 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL60.6 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL65.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL80.6 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR - 1%84.9 ft. JOM - Joint Offset Medium86 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - SL86.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H87 ft. TBD - Tap Break-In Defective, at 11 o'clock, -, , within 8 inches of joint: YES, 6", 6" - Open-30% ROOTS89.2 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS89.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped91.2 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - H92 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: NO - H96 ft. RFJ - Roots Fine Joint, from 11 to 01 o'clock, within 8 inches of joint: YESR - 1%106 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H106.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H107.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H116.2 ft. JOM - Joint Offset Medium116.4 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL117.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H121.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H131.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H131.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL136.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL140.6 ft. JOM - Joint Offset Medium146.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL150.6 ft. JOM - Joint Offset Medium151.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL156.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL166.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H176.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL187 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL192.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H194 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active194.5 ft. AMH - Downstream Manhole, Survey Ends - 3:10AM

Observation photos (7)

  • General Observation - 8" VCP

    9 ft. - General Observation - 8" VCP

  • Joint Offset Medium

    38.9 ft. - Joint Offset Medium

  • Joint Offset Medium

    84.9 ft. - Joint Offset Medium

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS

    89.2 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS

  • Joint Offset Medium

    116.2 ft. - Joint Offset Medium

  • Joint Offset Medium

    140.6 ft. - Joint Offset Medium

  • Joint Offset Medium

    150.6 ft. - Joint Offset Medium

Observations (46)

DistanceCodeObservation
116.2JOM
136.4FCSL
65.8FLSL
89.9TFCCapped
15FLH
60.6FCSL
106.3FLH
0MWM
176.7FLSL
86.3FLH
9MGO8" VCP
91.2FLH
89.2TFDOpen-90% ROOTS
0AMH2:25AM
58FLSLIGHT
86FLSL
150.6JOM
151.6FLSL
106FCH
107.4FCH
38.9JOM
156.7FLSL
121.4FLH
131.3FLH
116.4FCSL
58.6FCSL
80.6RFJ1%
140.6JOM
15FCHAIRLINE
55.5FCH
0MGOConn. @ Mh, 9 O' Clock. Active-OUTGOING LINE
194MGOConn. @ Mh, 9 O' Clock. Active
194.5AMH3:10AM
87TBDOpen-30% ROOTS
166.6FCH
131.3FLSL
0MWL
96RFJ1%
92FLH
0MGOConn. @ Mh, 3 O' Clock. Active
84.9JOM
53.1FLH
192.2FCH
117.6FCH
146.6FLSL
187FLSL

Properties (6)

custom_field_three
SLIGHT FRACTURES -MEDIUM JOINT OFFSETS
custom_field_two
3
customer
LACSD
datetime
2018-04-25T01:29:18-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false