Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 25, 2018, 08:40 AM
  • 29 0529A_29 0529_4252018_044548.mp4

Date
04/25/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01106
PipeID
P24584
Time
1:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0842
Sewer Name
29 19TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20180425MDM_19TH_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0529A
Downstream MH
29 0529
Dir. of Survey
Downstream
Length Surveyed
248.4 ft.
Total Length
248.5 ft.
Structural Index
2
Structural Quick
392A
Structural Rating
51
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
51
Pipe schematic from manhole 29 0529A to 29 0529
MH: 29 0529AMH: 29 0529downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area1 ft. MGO - General Observation - LAMPHOLE MH5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active9.9 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE9.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H10.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open12.5 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H33.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H37.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open45.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H50.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open51.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H57.4 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SLIGHT58.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active69.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H75.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H106.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open107.7 ft. MGO - General Observation - 8" VCP123.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H123.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H132.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H144.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H150.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H151.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open156 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H171.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H189.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H189.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H204.5 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - H205.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open207.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open209.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H237.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL248.5 ft. AMH - Downstream Manhole, Survey Ends - 5:25AM

Observation photos (2)

  • General Observation - LAMPHOLE MH

    1 ft. - General Observation - LAMPHOLE MH

  • General Observation - 8" VCP

    107.7 ft. - General Observation - 8" VCP

Observations (36)

DistanceCodeObservation
209.8FLH
171.4FCH
0AMH4:45AM
207.8TFOpen
123.2FLH
12.5FCH
45.3FCH
189.5FLH
10.7TFOpen
37.4TFOpen
75.2FCH
156FCH
0MWM
144.8FLH
9.9FCHAIRLINE
58.4TFActive
150.4FCH
123.2FLH
107.7MGO8" VCP
50.3TBOpen
57.4FCSLIGHT
237.1FLSL
132.4FLH
51.5FCH
0MWL
33.7FLH
106.2TFOpen
69.3FLH
1MGOLAMPHOLE MH
248.5AMH5:25AM
5TFActive
204.5FCH
189.5FCH
9.9FCH
205.5TFOpen
151.3TFOpen

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2018-04-25T01:40:26-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false