Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2018, 07:46 AM
  • 21 0619_21 0618_4212018_005429.mp4

Date
04/21/2018
W/O
0701654
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00786
PipeID
P15771
Time
12:46 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0832
Sewer Name
21 TRI-CITIES OUTFALL TRUNK
City
POMONA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20180421MDM_TRI_CITIES_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
21 0619
Downstream MH
21 0618
Dir. of Survey
Downstream
Length Surveyed
263.5 ft.
Total Length
263.5 ft.
Structural Index
2
Structural Quick
4135
Structural Rating
93
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
93
Pipe schematic from manhole 21 0619 to 21 0618
MH: 21 0619MH: 21 0618downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:50AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area9.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open18.6 ft. MGO - General Observation - 15" VCP22.9 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SLIGHT22.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE28 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL28 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL35.5 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H45.4 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL56.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL57.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H57.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H58.5 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SL65.8 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H83.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL83.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H89.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H103.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H105.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H113.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H138.3 ft. RPP - Repair Patch, from 02 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH138.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H138.3 ft. RPP - Repair Patch, from 02 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH140.9 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL145.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H156 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H158.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H173.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H173.6 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL181 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL183.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H183.4 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL188.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL191 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL191 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL200.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL205.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H231.1 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL231.1 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL233.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H233.6 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL243.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL248.8 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL248.8 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL251.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H255.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL260.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H260.9 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL262.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL263.5 ft. AMH - Downstream Manhole, Survey Ends - 1:30AM

Observation photos (4)

  • General Observation - 15" VCP

    18.6 ft. - General Observation - 15" VCP

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    83.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Repair Patch, from 02 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

    138.3 ft. - Repair Patch, from 02 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

  • Repair Patch, from 02 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

    138.3 ft. - Repair Patch, from 02 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

Observations (52)

DistanceCodeObservation
181FCSL
28FCSL
0AMH12:50AM
89.7FLH
45.4FCSL
0MWL
9.4TFOpen
260.9FCH
191FCSL
173.6FLH
83.9FLH
183.4FCH
56.4FCSL
83.1FCSL
262.9FLSL
231.1FCSL
140.9FCSL
233.6FLH
158.7FCH
28FCSL
251.2FCH
260.9FCSL
22.9FCSLIGHT
57.1FCH
183.4FCSL
191FCSL
138.3RPPCONCRETE PATCH
205.8FCH
173.6FCSL
0MWM
248.8FCSL
156FCH
263.5AMH1:30AM
103.1FCH
35.5FCH
18.6MGO15" VCP
65.8FCH
22.9FCHAIRLINE
188.4FMSL
57.6FCH
233.6FCSL
113.1FCH
105.9FLH
255.9FCSL
248.8FCSL
138.3FCH
231.1FCSL
243.5FCSL
200.9FCSL
145.8FCH
138.3RPPCONCRETE PATCH
58.5FCSL

Properties (6)

custom_field_three
HAIRLINE JOINT TO JOINT LONGER -CONCRETE REPAIR
custom_field_two
2
customer
LACSD
datetime
2018-04-21T00:46:39-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false