Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 20, 2018, 11:15 AM
  • 02 0402_02 0401_4202018_041745.mp4

Date
04/20/2018
W/O
0701224
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00250
PipeID
P02723
Time
4:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0831
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20180220MDM_DOWNEY_AVENUE_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 0402
Downstream MH
02 0401
Dir. of Survey
Downstream
Length Surveyed
349.8 ft.
Total Length
349.8 ft.
Structural Index
2
Structural Quick
4536
Structural Rating
110
O&M Index
3
O&M Quick
3221
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
118
Pipe schematic from manhole 02 0402 to 02 0401
MH: 02 0402MH: 02 0401downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL8.1 ft. MGO - General Observation - 15" VCP12.8 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL16.9 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE16.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL21.1 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL21.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H25.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL29.1 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL32.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL32.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL37.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL37.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H41.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL45.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL49.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 5" - Open50 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB53.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL57.2 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL61.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL65.3 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL65.3 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - SL66.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped69.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL73.2 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL77.9 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL77.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H81.3 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SL82.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open85.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL89.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H89.6 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL93.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL97.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL101.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL105.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL105.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL110 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL110 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H114.4 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL114.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL117.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H117.7 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SL121.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL126 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES - SL127 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped127 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped128 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open129.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL129.9 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - H131.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open134.1 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS134.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS134.1 ft. FL - Fracture Longitudinal, at 08 TO 4o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS134.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS160.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active163.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active204.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open208 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped212.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 03 o'clock, , within 8 inches of joint: YES212.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open236.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active249.3 ft. RML - Roots Medium Lateral, from 06 to 12 o'clock, 25 %, within 8 inches of joint: YES252.8 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6", 6" - Open256.2 ft. RML - Roots Medium Lateral, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES256.2 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open301.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active313.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped332.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open349.6 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Finish - 20% SLIGHT AT JOINTS349.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 95% HAIRLINE AT JOINTS349.6 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Finish - 20% HAIRLINE AT JOINTS349.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 95% SLIGHT AT JOINTS349.8 ft. AMH - Downstream Manhole, Survey Ends - 5:55AM

Observation photos (3)

  • General Observation - 15" VCP

    8.1 ft. - General Observation - 15" VCP

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL

    61.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL

  • Roots Medium Lateral, from 06 to 12 o'clock, 25 %, within 8 inches of joint: YES

    249.3 ft. - Roots Medium Lateral, from 06 to 12 o'clock, 25 %, within 8 inches of joint: YES

Observations (79)

DistanceCodeObservation
301.2TFActive
69.3FMSL
110FCSL
127TFCCapped
101.5FCSL
131.4TBOpen
0AMH4:40AM
349.6FL20% SLIGHT AT JOINTS
249.3RML
349.6FC95% HAIRLINE AT JOINTS
8.1MGO15" VCP
5FCSLIGHT
0MGOConn. @ Mh, 3 O' Clock. OPEN
134.1FLHAIRLINE AT JOINTS
77.9FCSL
97.5FCSL
21.1FCSL
16.9FCHAIRLINE
134.1FCSLIGHT AT JOINTS
332.8TFOpen
117.7FCH
110FCH
29.1FCSL
66.4TFCCapped
61.4FMSL
134.1FLSLIGHT AT JOINTS
114.4FCSL
53.2FCSL
204.4TBOpen
256.2RML
121.7FMSL
73.2FCSL
85.6FMSL
93.6FCSL
25.3FCSL
236.4TFActive
5FCSL
212.2DAGS
0MWL
57.2FCSL
49.7TFCOpen
160.2TBActive
77.9FCH
126FMSL
349.8AMH5:55AM
37.3FCSL
32.9FCSL
82.6TFOpen
65.3FCSL
208TFCCapped
16.9FLSL
50TFCSTUB
45.2FCSL
12.8FCSL
163.9TFActive
349.6FL20% HAIRLINE AT JOINTS
129.9FCSL
252.8TBOpen
114.4FLSL
212.2TFOpen
313.3TFCCapped
37.3FCH
32.9FCSL
256.2TBOpen
65.3FCSL
89.6FCH
349.6FC95% SLIGHT AT JOINTS
105.7FCSL
89.6FCSL
105.7FLSL
41.1FLSL
0MWM
81.3FCSL
134.1FCHAIRLINE AT JOINTS
21.1FCH
117.7FCSL
127TFCCapped
129.9FCH
128TBOpen

Properties (6)

custom_field_three
MULTIPLE SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-04-20T04:15:40-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false