Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 23, 2017, 08:36 AM
  • 02 1367_02 1366 _102317_013726.mp4

Date
10/23/2017
W/O
668911
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00277
PipeID
P03890
Time
1:36 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4997
Sewer Name
02 JANE STREET BRANCH TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
WO_668911_TV02072_NOV2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1366
Downstream MH
02 1367
Dir. of Survey
Upstream
Length Surveyed
318.7 ft.
Total Length
318.7 ft.
Structural Index
3
Structural Quick
413V
Structural Rating
472
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
474
Pipe schematic from manhole 02 1366 to 02 1367
MH: 02 1366MH: 02 1367upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 13672.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish11.3 ft. CM - Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES12.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"18.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"19.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES37.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES39 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"46.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES49.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish59.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start85.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES94.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES97.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish114.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"117 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"174.5 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"186.1 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"216.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"220.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES258.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"270.5 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"288.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"311.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start316 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start316.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start316.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES316.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start318.7 ft. AMH - Downstream Manhole, Survey Begins - 02 1366318.7 ft. MWM - Water Mark, 30 %of cross sectional area318.7 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (11)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    97.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    224 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    233.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    242.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    272.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    281.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    299.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    307.4 ft. - Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

Observations (35)

DistanceCodeObservation
144.2TF
204.3TF
48.2TFA
60.1TF
316SSS
300.6TF
97.8FM
272.5CM
306.1TF
7.5CM
299.3CM
318.7AMH02 1367
269.4CM
281.1CM
0AMH02 1366
316CM
180.8TF
233.3CM
2SSS
279.7TFA
30.4TF
2CM
316.3DAGS
259.2TF
0MWM
0MWL
224CM
242.6CM
307.4CM
221.1CM
132.6TFA
2CM
102.3TF
201.7TF
2.7DAGS

Properties (6)

additional_info
SC350351
custom_field_two
3
customer
LACSD
datetime
2017-10-23T01:36:24-07:00
documentation
PROPIPE
is_lateral_inspection
false