Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 21, 2017, 08:59 AM
  • 14 0258_14 0257_11212017_005956.mp4

Date
11/21/2017
W/O
668668
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00569
PipeID
P18315
Time
12:59 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5223
Sewer Name
14 AVENUE "H" TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
06
Purpose
Routine Assessment
Project
WO_668668_TV14069_NOV2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
14 0258
Downstream MH
14 0257
Dir. of Survey
Downstream
Length Surveyed
361.1 ft.
Total Length
361.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
144
Pipe schematic from manhole 14 0258 to 14 0257
MH: 14 0258MH: 14 0257downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 02580 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"360 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish361.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0257

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
360DAGS
0AMH14 0258
2DAGS
361.1AMH14 0257
16.8TF
0MWM
0MWL

Properties (6)

additional_info
SC346094
custom_field_two
4
customer
LACSD
datetime
2017-11-21T00:59:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false