- Date
- 11/20/2017
- W/O
- 668653
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00046
- PipeID
- P23211
- Time
- 11:51 PM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5041
- Sewer Name
- F JOINT OUTFALL F - UNIT 7D
- City
- CERRITOS
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 34
- Purpose
- Routine Assessment
- Project
- WO_668653_TV18080_NOV2017
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 33 in.
- Width
- 33 in.
- Upstream MH
- F 0313
- Downstream MH
- F 0312
- Dir. of Survey
- Downstream
- Length Surveyed
- 486.3 ft.
- Total Length
- 486.3 ft.
- Structural Index
- 3
- Structural Quick
- 3221
- Structural Rating
- 8
- O&M Index
- 3
- O&M Quick
- 3200
- O&M Rating
- 6
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole F 0313 to F 0312 Observation photos (5)

23.1 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

142.4 ft. - Infiltration Dripper, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

318.5 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

333.4 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

392.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start