Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2017, 04:53 PM
  • H 1489_H 1488 _291117_160739.mp4

Date
10/19/2017
W/O
668649
Weather
Dry
Operator/Surveyor
E RUIZ
Sewer ID
Z01206
PipeID
P16449
Time
9:53 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5141
Sewer Name
H JOINT OUTFALL H - UNIT 8M RELIEF
City
WEST COVINA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
30
Purpose
Routine Assessment
Project
WO_668649_TV22094_NOV2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
H 1489
Downstream MH
H 1488
Dir. of Survey
Downstream
Length Surveyed
660.4 ft.
Total Length
660.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 1489 to H 1488
MH: H 1489MH: H 1488downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 14890 ft. MGO - General Observation - MAG HO COATING START0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area4.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start198 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8", 8"655 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish655 ft. MGO - General Observation - MAG HO COATING FINISH660.4 ft. AMH - Downstream Manhole, Survey Ends - H 1488

Observation photos (1)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
198TFA
655SAP
655MGOMAG HO COATING FINISH
0AMHH 1489
4.1SAP
0MGOMAG HO COATING START
0MWM
0MWL
660.4AMHH 1488

Properties (6)

additional_info
SC346451
custom_field_two
3
customer
LACSD
datetime
2017-10-19T09:53:38-07:00
documentation
PROPIPE
is_lateral_inspection
false