Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 8, 2018, 08:50 AM
  • 08 046308 0477 District 08_112118123315.mpg

Date
10/08/2018
W/O
729415
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z00025
PipeID
P00535
Time
1:50 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6132
Sewer Name
08 216TH STREET RELOCATION TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_729415_TV08140_OCT2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
08 0463
Downstream MH
08 0477
Dir. of Survey
Downstream
Length Surveyed
796 ft.
Total Length
796 ft.
Structural Index
4
Structural Quick
5^3_
Structural Rating
1254
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
1258
Pipe schematic from manhole 08 0463 to 08 0477
MH: 08 0463MH: 08 0477downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04633.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.9 ft. MGO - General Observation - MAG COAT15.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start794.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish795.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish796 ft. AMH - Downstream Manhole, Survey Ends - 08 0477

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
3.9SAP
15.2SRV
794.1SAP
0MWM
796AMH08 0477
0MWL
3.9MGOMAG COAT
0AMH08 0463
795.3SRV

Properties (4)

additional_info
SC365202
custom_field_two
3
customer
LACSD
datetime
2018-10-08T01:50:00-07:00