Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2017, 08:05 AM
  • H 0746_H 0745_14072017_011347.mp4

Date
07/14/2017
W/O
640683
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00941
PipeID
P11155
Time
1:05 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4555
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
WEST COVINA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
30
Purpose
Routine Assessment
Project
WO_640683_TV18106_JUN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
H 0745
Downstream MH
H 0746
Dir. of Survey
Upstream
Length Surveyed
49.3 ft.
Total Length
49.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole H 0745 to H 0746
MH: H 0745MH: H 0746upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 07460 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish28.7 ft. MGO - General Observation - MAG COATING41.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start49.3 ft. MWM - Water Mark, 25 %of cross sectional area49.3 ft. MWL - Water Level, 20 %of cross sectional area49.3 ft. AMH - Downstream Manhole, Survey Begins - H 0745

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWM
0MWL
49.3AMHH 0746
49.3DAGS
20.6MGOMAG COATING
0AMHH 0745
8DAGS

Properties (6)

additional_info
SC345395
custom_field_two
4
customer
LACSD
datetime
2017-07-14T01:05:24-07:00
documentation
PROPIPE
is_lateral_inspection
false