Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2017, 09:11 AM
  • 18 0254_18 0253 _10072017_021140.mp4

Date
07/10/2017
W/O
640666
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14082
Time
2:11 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4639
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_640666_TV18003_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0254
Downstream MH
18 0253
Dir. of Survey
Downstream
Length Surveyed
38.6 ft.
Total Length
38.6 ft.
Structural Index
2
Structural Quick
3121
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0254 to 18 0253
MH: 18 0254MH: 18 0253downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02540 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE0 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE3.2 ft. CC - Crack Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES7.7 ft. CC - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES12.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES23.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES32 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES38.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0253

Observation photos (5)

  • Crack Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES

    3.2 ft. - Crack Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    7.7 ft. - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    12.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    23.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

    32 ft. - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MWL
0AMH18 0254
7.7CC
0MWM
38.6AMH18 0253
3.2CC
32CC
0MGOCONNECTION AT MH 9 ACTIVE
0MGOCONNECTION AT MH 3 ACTIVE
23.9CM
12.3CL

Properties (6)

additional_info
SC345385
custom_field_two
3
customer
LACSD
datetime
2017-07-10T02:11:09-07:00
documentation
PROPIPE
is_lateral_inspection
false