Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2017, 09:48 AM
  • 18 0251_18 0250 _10072017_024848.mp4

Date
07/10/2017
W/O
640666
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14079
Time
2:48 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4639
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_640666_TV18003_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0251
Downstream MH
18 0250
Dir. of Survey
Downstream
Length Surveyed
106.4 ft.
Total Length
106.5 ft.
Structural Index
2
Structural Quick
3426
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 18 0251 to 18 0250
MH: 18 0251MH: 18 0250downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02510 ft. MWM - Water Mark, 20 %of cross sectional area5.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES23.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES24.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"35.7 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES44 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES60.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES71.8 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES76.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES80.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES84.1 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES92.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES101.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"106.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0250106.5 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE106.5 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE

Observation photos (10)

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    5.6 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    23.4 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    35.7 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    44 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    60.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    71.8 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    76.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    80.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    84.1 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    92.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
44CL
84.1CL
60.1CL
24.7TFC
0MWL
106.5AMH18 0250
0AMH18 0251
92.5CL
101.7TFC
23.4CM
106.5MGOCONNECTION AT MH 3 ACTIVE
5.6CL
80.2CL
0MWM
71.8CM
35.7CM
106.5MGOCONNECTION AT MH 9 ACTIVE
76.1CM

Properties (6)

additional_info
SC345385
custom_field_two
3
customer
LACSD
datetime
2017-07-10T02:48:33-07:00
documentation
PROPIPE
is_lateral_inspection
false