Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 12, 2017, 06:55 AM
  • 02 1392_02 1391 _12052017_011419.mp4

Date
05/11/2017
W/O
635640
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00349
PipeID
P02963
Time
11:55 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4451
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_635640_TV02220_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
02 1392
Downstream MH
02 1391
Dir. of Survey
Downstream
Length Surveyed
599.7 ft.
Total Length
599.7 ft.
Structural Index
4
Structural Quick
5W3W
Structural Rating
952
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
952
Pipe schematic from manhole 02 1392 to 02 1391
MH: 02 1392MH: 02 1391downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13922 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start596.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish596.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish599.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1391

Observation photos (2)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWL
596.1SRV
2SRV
0MWM
2SAP
0AMH02 1392
596.1SAP
599.7AMH02 1391

Properties (6)

additional_info
SC345227
custom_field_two
2
customer
LACSD
datetime
2017-05-11T23:55:20-07:00
documentation
PRO PIPE
is_lateral_inspection
false