Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 12, 2017, 06:17 AM
  • 02 1393_02 1392 _11052017_235455.mp4

Date
05/11/2017
W/O
635640
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00349
PipeID
P02964
Time
11:17 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4451
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_635640_TV02220_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
02 1393
Downstream MH
02 1392
Dir. of Survey
Downstream
Length Surveyed
905.1 ft.
Total Length
905.1 ft.
Structural Index
4
Structural Quick
5\3c
Structural Rating
1265
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1265
Pipe schematic from manhole 02 1393 to 02 1392
MH: 02 1393MH: 02 1392downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 02 13930 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start175.7 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start852.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"900.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish900.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish905.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1392

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    175.7 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
905.1AMH02 1392
852.1TBA
175.7SRV
900.5SRV
0AMH02 1393
2SAP
900.5SAP
0MWL

Properties (6)

additional_info
SC345227
custom_field_two
2
customer
LACSD
datetime
2017-05-11T23:17:12-07:00
documentation
PRO PIPE
is_lateral_inspection
false