Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2017, 04:40 AM
  • 02 141302 1412 District 02_053117.mpg

Date
05/31/2017
W/O
635640
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02984
Time
9:40 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4612
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
WO_635640_TV02220_MAY2017
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
63 in.
Upstream MH
02 1413
Downstream MH
02 1412
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 1413 to 02 1412
MH: 02 1413MH: 02 1412downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14130 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area2.1 ft. MSA - Survey Abandoned - DOWN LEG OF THE U/S SIPHON2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

Observation photos (3)

  • Survey Abandoned - DOWN LEG OF THE U/S SIPHON

    2.1 ft. - Survey Abandoned - DOWN LEG OF THE U/S SIPHON

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
2.1MSADOWN LEG OF THE U/S SIPHON
2.1SRV
2.1SAP
0AMH02 1413
0MWL
0MWM

Properties (6)

additional_info
SC345324
custom_field_two
2
customer
LACSD
datetime
2017-05-31T21:40:07-07:00
documentation
PROPIPE
is_lateral_inspection
false